Motors, transformers and ballasts draw reactive power from the network. It does no useful work but loads the lines and the transformer, and above a certain ratio it appears on the bill as a reactive energy charge. Power factor correction supplies that reactive power locally with capacitors.
Basic terms
- Active power (P, kW): power converted to work
- Reactive power (Q, kVAr): power drawn for magnetic fields
- Apparent power (S, kVA): total power drawn from the network
- cos φ = P / S: the power factor; the closer to 1 the better
Required capacitor rating
Qc = P × (tan φ₁ − tan φ₂)
φ₁ is the angle of the present power factor and φ₂ that of the target.
Example
100 kW load, present cos φ = 0.75, target cos φ = 0.98:
- tan φ₁ = 0.882 → present reactive power 88.2 kVAr
- tan φ₂ = 0.203 → remaining reactive power 20.3 kVAr
- Qc = 100 × (0.882 − 0.203) = 67.9 kVAr
The next standard rating, 75 kVAr, is chosen. After correction the line current falls from about 192 A to 147 A, a 23.5% reduction that relieves the transformer and cables.
Monthly ratio check
Two ratios are calculated from the meter readings on the bill:
- Inductive ratio = inductive reactive energy (kVArh) / active energy (kWh)
- Capacitive ratio = capacitive reactive energy (kVArh) / active energy (kWh)
In Turkey these are expected not to exceed 20% and 15% respectively; above that a reactive energy charge applies. Limits can change, so confirm the current values with your distribution company.
Practical notes
- If the load varies during the day, use an automatic stepped panel rather than fixed capacitors, otherwise you will go capacitive at low load.
- With harmonic-producing loads such as drives and UPS units, a detuned solution may be needed.
- Targeting 0.95–0.98 instead of 1.00 lowers the risk of over-compensation.
Quick calculation
Use the Power Factor Correction Calculator to find the required kVAr, the standard bank size and your monthly inductive/capacitive ratios.