« Tools · Electrical Calculators
Power Factor Correction Calculator
Enter the active power and present and target power factor to find the capacitor rating (kVAr) you need. The second mode checks inductive/capacitive reactive ratios from monthly meter readings.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- In "Power and cos φ" mode enter active power, present cos φ and target cos φ.
- Check voltage and frequency; the required kVAr, a standard capacitor bank and capacitance per phase appear.
- In "Monthly ratio check" mode enter monthly kWh and inductive/capacitive kVArh to see the ratios.
Method and assumptions
- Required rating: Qc = P · (tan φ₁ − tan φ₂). For delta-connected capacitors the capacitance per phase is C = Qc / (3·ω·U²).
- Monthly check: inductive ratio = kVArh(inductive) / kWh, capacitive ratio = kVArh(capacitive) / kWh. Turkish distribution rules take these not to exceed 20 % and 15 % respectively; limits may change, so confirm with current regulations and your distribution company.
- On networks with harmonics, detuned reactors and a suitable voltage class may be needed; this is not covered here.
Worked example
Active power 100 kW, present power factor 0.75, target power factor 0.98, 400 V, 50 Hz supply.
Required reactive power: Qc = 100 · (tan φ₁ − tan φ₂) = 100 · (0.882 − 0.203) = 67.9 kVAr. Rounded up to a standard stepped bank, 75 kVAr is chosen.
| Quantity | Before | After |
|---|---|---|
| Apparent power | 133.3 kVA | 102.0 kVA |
| Line current | 192.5 A | 147.3 A |
| Current reduction | 23.5% |
For a delta-connected capacitor the capacitance per phase is about 450 µF. The lower current eases the load on cables, transformer and panel.
Multiplier table: kVAr needed per kW
| Present PF | Target 0.95 | Target 0.98 |
|---|---|---|
| 0.70 | 0.692 | 0.817 |
| 0.75 | 0.553 | 0.679 |
| 0.80 | 0.421 | 0.547 |
| 0.85 | 0.291 | 0.417 |
| 0.90 | 0.156 | 0.281 |
Multiply the active power (kW) by the factor in the table to get the required kVAr. For example 100 kW and 0.75 → 0.98 gives 100 × 0.679 = 67.9 kVAr.
Common mistakes
- Over-compensation: too many capacitors push the plant into the capacitive region; if the capacitive ratio limit is exceeded, a charge may apply.
- Fixed bank with a varying load: if the load changes constantly you need an automatic stepped panel.
- Ignoring harmonics: where drives and rectifiers create harmonics, a detuned (reactor) bank may be needed.
- Neglecting voltage: the capacitor voltage class must suit the supply voltage and possible swells.
- Not looking at the meter values: the target is not just the power factor but the inductive and capacitive ratios over the billing period; the second mode checks this.
Frequently asked questions
What target cos φ should I use?
Usually 0.95–0.98. Getting too close to 1 increases the risk of entering the capacitive region.
Why is the standard bank larger than the calculated value?
Capacitor banks come in fixed steps; the next standard rating above the required kVAr is suggested. In a real plant an automatic stepped panel is preferred.
What is capacitance per phase for?
It is the total capacitance of each phase leg when capacitors are delta-connected, used as a check value when selecting from a manufacturer.
Why do power factor correction?
It reduces reactive power, which lowers line current, losses and transformer load, and avoids charges for plants that exceed the inductive and capacitive ratio limits.
What are the ratio limits?
Distribution rules take inductive and capacitive ratios not exceeding 20% and 15% respectively. Limits can change, so check current rules and your distribution company.
Can I connect the capacitors myself?
No. A capacitor bank needs careful selection, protection and installation; have a qualified engineer or electrical contractor do it.
Guide: How to Calculate Power Factor Correction: kVAr Sizing with an Example