Short-Circuit Current Calculator
Enter the transformer rating, voltage and impedance voltage (uk) to see the three-phase short-circuit and peak currents at the transformer terminals and, optionally, at the end of a cable.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Enter the transformer rating (kVA), secondary voltage and uk (%) from the nameplate.
- For the value at the end of a run enter cable length, size, parallel count and material; set the length to 0 for the transformer terminals only.
- The initial short-circuit current (Ik″) and peak current (ip) appear; compare them when selecting breakers and busbars.
Method and assumptions
- Transformer impedance: Zt = uk · U² / S. Short-circuit current: Ik″ = c · U / (√3 · Z). The voltage factor c defaults to 1.05 (low voltage, maximum fault).
- The upstream network is taken as infinite (result on the safe, slightly high side). R/Z = 0.25 is assumed for the transformer. Cable resistance uses 20 °C values ρ(Cu) = 0.0185, ρ(Al) = 0.0294 Ω·mm²/m; reactance 0.08 mΩ/m.
- Peak current: ip = κ · √2 · Ik″ with κ = 1.02 + 0.98·e^(−3R/X). Motor contribution, phase-to-earth faults and minimum fault current are not included.
Worked example
A 630 kVA, 400 V, uk = 4% transformer followed by a 30 m, 95 mm² copper cable. Voltage factor c = 1.05, the upstream network is taken as infinitely strong.
Transformer rated current In = 630,000 / (√3 · 400) = 909 A. At the transformer secondary the short-circuit current is 23.87 kA and the peak current 49.68 kA. At the end of the cable, the added impedance lowers the short-circuit current to 16.35 kA and the peak current to 26.49 kA. The panel and breaker are selected against these values.
Secondary short-circuit current for typical transformers
| Transformer | uk | In (400 V) | Ik″ (at terminals) |
|---|---|---|---|
| 400 kVA | 4% | 577 A | 15.2 kA |
| 630 kVA | 4% | 909 A | 23.9 kA |
| 800 kVA | 6% | 1,155 A | 20.2 kA |
| 1000 kVA | 6% | 1,443 A | 25.3 kA |
| 1250 kVA | 6% | 1,804 A | 31.6 kA |
Values use the tool's assumptions (c = 1.05, infinite network). The uk values are typical for distribution transformers; check your own transformer's nameplate.
How to use the result
- The breaker's short-circuit breaking capacity (Icu/Ics) must exceed the calculated Ik″.
- Busbars and cables must withstand the calculated current for the clearing time.
- The peak current ip sets the electrodynamic stress; panel and busbar ratings are compared against it.
- The short-circuit current at the end of a line affects the tripping time of the protective device.
Common mistakes
- Mistaking rated current for short-circuit current: the fault current is roughly 1.05/uk times the rated current, i.e. 17-26 times.
- Ignoring the cable: on long runs impedance cuts the current noticeably, which matters for both rating and protection.
- Forgetting the minimum short-circuit current: this tool gives the maximum; the minimum is also needed to check tripping.
- Ignoring motor contribution: large motors add to the fault current; it is not included here.
- Treating the result as final: it is a preliminary calculation; use the relevant standard and network data for a real design.
Frequently asked questions
What is uk?
The transformer's relative impedance voltage (given in % on the nameplate). Typically 4–6 % for distribution transformers; the lower it is, the higher the fault current.
What do I compare this value with?
The breaker's short-circuit breaking capacity (Icu/Ics) and the busbar withstand current must exceed the calculated value.
Why does fault current fall with cable length?
The cable impedance adds to the circuit and limits the current; this also affects the tripping condition of the protective device at the far end.
What do I compare it with?
The breaker's short-circuit breaking capacity and the busbars' withstand current. A device rated below the calculated value cannot be used.
Why does the fault current fall with a longer cable?
Cable impedance is added to the circuit and limits the current; this also affects the tripping condition of the protective device at the end of the line.
Why assume an infinitely strong upstream network?
When the utility's fault level is unknown, this assumption leaves the result on the safe, slightly high side. With network data the real value is lower.