« Tools · Electrical Calculators
Circuit Breaker (MCB) Sizing
Enter the load current (and the cable's current-carrying capacity if you know it) to see the right standard MCB rating and trip range.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Enter the load current (Ib).
- If known, enter the cable's current-carrying capacity (Iz) from the Cable Size or Ampacity Table tool.
- Choose the trip curve (B, C, D); the result shows In, the instantaneous trip range and the compatibility check.
Method and assumptions
- Overload protection rule: Ib ≤ In ≤ Iz. The breaker must not be below the load current nor above the cable's capacity.
- Instantaneous trip ranges (IEC 60898-1): curve B 3-5 × In, curve C 5-10 × In, curve D 10-20 × In.
- The short-circuit breaking capacity (e.g. 6 kA) must exceed the prospective short-circuit current at the point; check with the Short-Circuit Current tool.
Example
The current of a three-phase 15 kW load is about 25.5 A. The smallest standard value not below it is 32 A; on curve C the instantaneous trip is 160-320 A. With a 4 mm² Cu cable (method C, 32 A) In ≤ Iz holds; with 2.5 mm² (24 A) a 32 A breaker would not be suitable.
Largest MCB by cable size (Cu, PVC, method C)
| Size (mm²) | Iz (A) | Largest standard MCB |
|---|---|---|
| 1.5 | 17.5 | 16 A |
| 2.5 | 24 | 20 A |
| 4 | 32 | 32 A |
| 6 | 41 | 40 A |
| 10 | 57 | 50 A |
| 16 | 76 | 63 A |
| 25 | 96 | 80 A |
| 35 | 119 | 100 A |
Values assume 30 °C ambient, a single circuit and method C. With grouping or high temperature Iz falls; use the correction factor (k) in the Cable Size tool.
Common mistakes
- Choosing a breaker larger than the cable: remember In ≤ Iz.
- Choosing the curve without considering the load: curve B trips needlessly on high-inrush loads.
- Not checking breaking capacity: a 6 kA breaker is inadequate where the short-circuit current is higher.
Frequently asked questions
How do I choose curve B, C or D?
B for lighting and long lines, C for general sockets and small motor circuits, D for loads with high inrush (transformers, large motors). The final choice depends on equipment and project requirements.
What if the breaker is larger than the cable?
Under overload the cable can overheat before the breaker trips. So In must not exceed the cable capacity (Iz); otherwise increase the cable size.
Is this tool enough for motors?
Motors need starting-current handling and thermal protection; use the Motor Current, Fuse and Contactor tool.
Guide: How to Choose a Circuit Breaker: B, C, D Curves and Cable Match