« Tools · Electrical Calculators

Cable Current-Carrying Capacity Table

Pick the conductor and installation method to see the capacities by size, or type your current to find the smallest size.

Calculations run in your browser; the data you enter is never sent to any server.

Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.

Get a Quote »
Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.

How to use

  1. Choose the conductor (Cu or Al) and the installation method.
  2. Optionally type your load current; the smallest adequate size is highlighted.
  3. Use the Cable Size tool for voltage drop and the correction factor.

Method and assumptions

  • Values are for IEC 60364-5-52 reference conditions: PVC insulation (70 °C), 3 loaded conductors, 30 °C ambient, a single circuit.
  • High ambient temperature and grouping reduce capacity; the Cable Size tool accounts for them with the correction factor (k).
  • Current capacity alone is not enough; voltage drop, short-circuit withstand and the protective device also decide the size.

Copper cable (PVC, 30 °C)

Size (mm²)B2 (A)C (A)E (A)
1.51517.518.5
2.5202425
4273234
6344143
10465760
16627680
258096101
3599119126
50118144153
70149184196
95179223238
120206259276
150225299319
185255341364
240297403430
300339464497

Aluminium cable (PVC, 30 °C)

Size (mm²)B2 (A)C (A)E (A)
16485961
25627378
35779096
5092110117
70116140150
95139170183
120160197212
150176227245
185199259280
240232305330
300265351381

Ambient temperature correction (typical for PVC)

Ambient temperatureFactor
30 °C1.00
35 °C0.94
40 °C0.87
45 °C0.79
50 °C0.71

Example: 25 mm² Cu, method C carries 96 A; at 40 °C ambient 96 × 0.87 ≈ 83.5 A is usable.

Common mistakes

  • Choosing size from the current table only: on long runs voltage drop governs.
  • Picking the wrong installation method: the same size carries different current in air and in conduit.
  • Laying several circuits together: a grouping factor is needed.

Frequently asked questions

How many amps does a 2.5 mm² copper cable carry?

In this table 24 A for method C, 20 A for B2 and 25 A for E (PVC, 30 °C).

Why does aluminium start at 16 mm²?

Aluminium is not commonly used in small sizes; the table shows 16 mm² and above.

What if the ambient temperature is 40 °C?

A typical correction factor for PVC at 40 °C is about 0.87; multiply the table value by it.

More tools