Cable Current-Carrying Capacity Table
Pick the conductor and installation method to see the capacities by size, or type your current to find the smallest size.
Calculations run in your browser; the data you enter is never sent to any server.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.
How to use
- Choose the conductor (Cu or Al) and the installation method.
- Optionally type your load current; the smallest adequate size is highlighted.
- Use the Cable Size tool for voltage drop and the correction factor.
Method and assumptions
- Values are for IEC 60364-5-52 reference conditions: PVC insulation (70 °C), 3 loaded conductors, 30 °C ambient, a single circuit.
- High ambient temperature and grouping reduce capacity; the Cable Size tool accounts for them with the correction factor (k).
- Current capacity alone is not enough; voltage drop, short-circuit withstand and the protective device also decide the size.
Copper cable (PVC, 30 °C)
| Size (mm²) | B2 (A) | C (A) | E (A) |
|---|---|---|---|
| 1.5 | 15 | 17.5 | 18.5 |
| 2.5 | 20 | 24 | 25 |
| 4 | 27 | 32 | 34 |
| 6 | 34 | 41 | 43 |
| 10 | 46 | 57 | 60 |
| 16 | 62 | 76 | 80 |
| 25 | 80 | 96 | 101 |
| 35 | 99 | 119 | 126 |
| 50 | 118 | 144 | 153 |
| 70 | 149 | 184 | 196 |
| 95 | 179 | 223 | 238 |
| 120 | 206 | 259 | 276 |
| 150 | 225 | 299 | 319 |
| 185 | 255 | 341 | 364 |
| 240 | 297 | 403 | 430 |
| 300 | 339 | 464 | 497 |
Aluminium cable (PVC, 30 °C)
| Size (mm²) | B2 (A) | C (A) | E (A) |
|---|---|---|---|
| 16 | 48 | 59 | 61 |
| 25 | 62 | 73 | 78 |
| 35 | 77 | 90 | 96 |
| 50 | 92 | 110 | 117 |
| 70 | 116 | 140 | 150 |
| 95 | 139 | 170 | 183 |
| 120 | 160 | 197 | 212 |
| 150 | 176 | 227 | 245 |
| 185 | 199 | 259 | 280 |
| 240 | 232 | 305 | 330 |
| 300 | 265 | 351 | 381 |
Ambient temperature correction (typical for PVC)
| Ambient temperature | Factor |
|---|---|
| 30 °C | 1.00 |
| 35 °C | 0.94 |
| 40 °C | 0.87 |
| 45 °C | 0.79 |
| 50 °C | 0.71 |
Example: 25 mm² Cu, method C carries 96 A; at 40 °C ambient 96 × 0.87 ≈ 83.5 A is usable.
Common mistakes
- Choosing size from the current table only: on long runs voltage drop governs.
- Picking the wrong installation method: the same size carries different current in air and in conduit.
- Laying several circuits together: a grouping factor is needed.
Frequently asked questions
How many amps does a 2.5 mm² copper cable carry?
In this table 24 A for method C, 20 A for B2 and 25 A for E (PVC, 30 °C).
Why does aluminium start at 16 mm²?
Aluminium is not commonly used in small sizes; the table shows 16 mm² and above.
What if the ambient temperature is 40 °C?
A typical correction factor for PVC at 40 °C is about 0.87; multiply the table value by it.