« Tools · Electrical Calculators

kW – kVA – Amps Converter

Enter the one value you know (kW, kVA or A); the others are calculated from the voltage and power factor.

Calculations run in your browser; the data you enter is never sent to any server.

Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.

Get a Quote »
Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.

How to use

  1. Choose the system (three-phase, single-phase or DC).
  2. Pick the value you know (kW, kVA or A), then enter the number, voltage and power factor.
  3. Real power, apparent power, reactive power and current are calculated instantly.

Method and assumptions

  • Three-phase: P = √3 × U × I × cos φ. Single-phase: P = U × I × cos φ. DC: P = U × I (cos φ = 1).
  • For three-phase enter the line-to-line voltage (e.g. 400 V), for single-phase the phase-neutral voltage (e.g. 230 V).
  • Motor and cable selection also needs efficiency and starting current; see the Motor Current and Cable Size tools.

Examples

KnownSystemResult
15 kW, 400 V, cos φ 0.85Three-phase17.6 kVA, 25.5 A
100 A, 400 V, cos φ 0.8Three-phase69.3 kVA, 55.4 kW
5 kVA, 230 V, cos φ 0.9Single-phase4.5 kW, 21.7 A
2.4 kW, 24 VDC100 A

Quick table: three-phase 400 V, cos φ = 0.85

Power (kW)Current (A)
1.11.9
2.23.7
35.1
5.59.3
7.512.7
1118.7
1525.5
2237.4
3050.9
4576.4

The table ignores efficiency (it gives load current). For motors the real current is higher by the efficiency; use the motor tool.

Common mistakes

  • Taking power factor as 1: current comes out too low; 0.8-0.9 is typical for induction motors.
  • Mixing line and phase voltage: enter 400 V for three-phase and 230 V for single-phase.
  • Treating kVA as kW: transformers and generators are rated in kVA, motors and heaters in kW.

Frequently asked questions

How many amps is 1 kW?

About 1.7 A at three-phase 400 V and power factor 0.85. About 4.35 A at single-phase 230 V and power factor 1.

What is the difference between kVA and kW?

kVA is apparent power, kW is real (useful) power. The ratio is the power factor: kW = kVA × cos φ.

Why is √3 used in three-phase?

The line-to-line voltage is √3 times the phase voltage because of the 120° phase shift; the factor appears in the total power.

Guide: How Many Amps Is a kW? kW, kVA and Amps Conversion (Single and Three Phase)

More tools