« Tools · Electrical Calculators

Motor Current, Fuse & Contactor Selection

Enter motor power (kW, PS or HP), voltage, cos φ and efficiency; the rated current, recommended gG fuse, AC-3 contactor and thermal relay setting are calculated.

Calculations run in your browser; the data you enter is never sent to any server.

Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.

Get a Quote »
Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.

How to use

  1. Enter the motor power and its unit (nameplate shaft power).
  2. Enter voltage, cos φ and efficiency from the nameplate; use the defaults if unknown.
  3. Choose the starting method; fuse, contactor and relay suggestions appear.

Method and assumptions

  • Rated current: In = P / (√3 · U · cos φ · η). 1 PS = 0.7355 kW and 1 HP = 0.7457 kW are used.
  • The gG fuse is the nearest standard rating not below In times a starting factor (DOL 2.0×, heavy start 2.5×, star-delta 1.6×, soft starter 1.6×, drive 1.5×). These are typical guideline values; the manufacturer's table prevails.
  • The AC-3 contactor current is ≥ In (star-delta: main/delta contactors ≥ 0.58·In, star contactor ≥ 0.33·In). The thermal relay is set to the rated current (0.58·In in star-delta).

Example 1: 11 kW motor, direct on line

11 kW, 400 V, power factor 0.85, efficiency 0.90. Rated current In = 11,000 / (√3 · 400 · 0.85 · 0.90) = 20.8 A. Direct on line uses a factor of 2.0, so the nearest standard gG fuse not below 41.6 A is 50 A. The AC-3 contactor current must exceed In: 25 A.

Example 2: 30 kW motor, star-delta

30 kW, power factor 0.88, efficiency 0.92: In = 53.5 A. Star-delta uses a factor of 1.6, so a 100 A gG fuse is chosen. The main and delta contactors need at least 0.58 · In = 31.0 → 32 A and the star contactor at least 0.33 · In = 17.6 → 18 A. The thermal relay is set to 0.58 · In = 31.0 A.

Quick table for typical motors (direct on line, 400 V)

Power (kW)In (A)gG fuse (A)AC-3 contactor (A)
1.52.869
35.7169
5.510.42512
7.514.23218
1120.85025
1528.36332
2241.510050
3056.612565
3769.816080
55103.8250115
75141.5315150

The table assumes power factor 0.85 and efficiency 0.90. The motor nameplate always governs; fuse and contactor values are typical guidance and the manufacturer's tables prevail.

Common mistakes

  • Estimating the current from power alone: current depends on power factor and efficiency; enter the nameplate current if you have it.
  • Choosing the fuse equal to In: the starting current makes the fuse noticeably larger than In; motor protection is done by the thermal relay.
  • Choosing the cable from the fuse: the cable follows the motor current and voltage drop (see the cable size tool).
  • Using the same contactor for all in star-delta: the star contactor can be smaller.

Frequently asked questions

How do I set the thermal relay?

To the rated current on the nameplate; in star-delta to 0.58 times the line current. The value shown follows this rule.

Why is the fuse much larger than In?

A gG fuse must not blow during motor starting, so 1.5–2.5 times In is chosen. Overload protection is provided by the thermal relay or motor protection breaker.

How do I find the cable size?

Enter the calculated rated current as the current in the cable size tool to check size and voltage drop for your length.

Where do I set the thermal relay?

To the nameplate current (0.58 · In in star-delta); check also against cable and motor protection.

How are fuses chosen with a soft starter or drive?

The tool uses a factor by starting type (soft starter 1.6×, drive 1.5×); the device manufacturer's recommendation governs.

Can I enter PS or HP?

Yes. 1 PS = 0.7355 kW and 1 HP = 0.7457 kW are used.

Guide: How to Select Motor Current, Fuse and Contactor: Worked Example