« Tools · Electrical Calculators
Motor Current, Fuse & Contactor Selection
Enter motor power (kW, PS or HP), voltage, cos φ and efficiency; the rated current, recommended gG fuse, AC-3 contactor and thermal relay setting are calculated.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Enter the motor power and its unit (nameplate shaft power).
- Enter voltage, cos φ and efficiency from the nameplate; use the defaults if unknown.
- Choose the starting method; fuse, contactor and relay suggestions appear.
Method and assumptions
- Rated current: In = P / (√3 · U · cos φ · η). 1 PS = 0.7355 kW and 1 HP = 0.7457 kW are used.
- The gG fuse is the nearest standard rating not below In times a starting factor (DOL 2.0×, heavy start 2.5×, star-delta 1.6×, soft starter 1.6×, drive 1.5×). These are typical guideline values; the manufacturer's table prevails.
- The AC-3 contactor current is ≥ In (star-delta: main/delta contactors ≥ 0.58·In, star contactor ≥ 0.33·In). The thermal relay is set to the rated current (0.58·In in star-delta).
Example 1: 11 kW motor, direct on line
11 kW, 400 V, power factor 0.85, efficiency 0.90. Rated current In = 11,000 / (√3 · 400 · 0.85 · 0.90) = 20.8 A. Direct on line uses a factor of 2.0, so the nearest standard gG fuse not below 41.6 A is 50 A. The AC-3 contactor current must exceed In: 25 A.
Example 2: 30 kW motor, star-delta
30 kW, power factor 0.88, efficiency 0.92: In = 53.5 A. Star-delta uses a factor of 1.6, so a 100 A gG fuse is chosen. The main and delta contactors need at least 0.58 · In = 31.0 → 32 A and the star contactor at least 0.33 · In = 17.6 → 18 A. The thermal relay is set to 0.58 · In = 31.0 A.
Quick table for typical motors (direct on line, 400 V)
| Power (kW) | In (A) | gG fuse (A) | AC-3 contactor (A) |
|---|---|---|---|
| 1.5 | 2.8 | 6 | 9 |
| 3 | 5.7 | 16 | 9 |
| 5.5 | 10.4 | 25 | 12 |
| 7.5 | 14.2 | 32 | 18 |
| 11 | 20.8 | 50 | 25 |
| 15 | 28.3 | 63 | 32 |
| 22 | 41.5 | 100 | 50 |
| 30 | 56.6 | 125 | 65 |
| 37 | 69.8 | 160 | 80 |
| 55 | 103.8 | 250 | 115 |
| 75 | 141.5 | 315 | 150 |
The table assumes power factor 0.85 and efficiency 0.90. The motor nameplate always governs; fuse and contactor values are typical guidance and the manufacturer's tables prevail.
Common mistakes
- Estimating the current from power alone: current depends on power factor and efficiency; enter the nameplate current if you have it.
- Choosing the fuse equal to In: the starting current makes the fuse noticeably larger than In; motor protection is done by the thermal relay.
- Choosing the cable from the fuse: the cable follows the motor current and voltage drop (see the cable size tool).
- Using the same contactor for all in star-delta: the star contactor can be smaller.
Frequently asked questions
How do I set the thermal relay?
To the rated current on the nameplate; in star-delta to 0.58 times the line current. The value shown follows this rule.
Why is the fuse much larger than In?
A gG fuse must not blow during motor starting, so 1.5–2.5 times In is chosen. Overload protection is provided by the thermal relay or motor protection breaker.
How do I find the cable size?
Enter the calculated rated current as the current in the cable size tool to check size and voltage drop for your length.
Where do I set the thermal relay?
To the nameplate current (0.58 · In in star-delta); check also against cable and motor protection.
How are fuses chosen with a soft starter or drive?
The tool uses a factor by starting type (soft starter 1.6×, drive 1.5×); the device manufacturer's recommendation governs.
Can I enter PS or HP?
Yes. 1 PS = 0.7355 kW and 1 HP = 0.7457 kW are used.