Cable Size & Voltage Drop Calculator
Enter the load power or current, the run length and the installation method to see the standard cable size that meets both current-carrying capacity and the allowed voltage drop.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Choose the system (three-phase, single-phase, DC) and enter the load as power (kW) or current (A).
- Enter voltage, power factor, run length, conductor material and installation method.
- If needed, set the correction factor (k) for ambient temperature/grouping and the allowed voltage drop; the recommended size and a table of all sizes appear.
Method and assumptions
- Current ratings follow IEC 60364-5-52 for PVC insulated (70 °C) cables, three loaded conductors, 30 °C ambient. The same table is used for single-phase and DC, so the result is on the safe side.
- Voltage drop: three-phase ΔU = √3·I·L·(R·cos φ + X·sin φ); single-phase and DC 2·I·L·(…). R = ρ/S with ρ(Cu) = 0.0225 and ρ(Al) = 0.036 Ω·mm²/m (70 °C conductor) and X = 0.08 mΩ/m.
- Aluminium sizes below 16 mm² are not listed. Short-circuit withstand, earthing, harmonics and conduit fill are not included.
Example 1: a short run where current governs
15 kW, 400 V three-phase load, power factor 0.85, run length 50 m, copper cable, installation method C, correction factor 1, permitted voltage drop 3%.
Load current I = 15,000 / (√3 · 400 · 0.85) = 25.5 A. A 2.5 mm² cable carries 24 A, which is not enough (and the voltage drop would be 4.24%). A 4 mm² cable carries 32 A with a 2.66% drop, so the result is 4 mm². Current is the deciding criterion.
Example 2: a long run where voltage drop governs
100 A, 400 V, power factor 0.9, run length 300 m, copper cable, method C. A 95 mm² cable carries 223 A, far more than needed for current, but the voltage drop is 3.22% and exceeds the 3% limit. A 120 mm² cable is chosen. On long runs voltage drop is usually the deciding criterion.
Current-carrying capacity table (copper, A)
| Size (mm²) | B2 | C | E |
|---|---|---|---|
| 1.5 | 15 | 17.5 | 18.5 |
| 2.5 | 20 | 24 | 25 |
| 4 | 27 | 32 | 34 |
| 6 | 34 | 41 | 43 |
| 10 | 46 | 57 | 60 |
| 16 | 62 | 76 | 80 |
| 25 | 80 | 96 | 101 |
| 35 | 99 | 119 | 126 |
| 50 | 118 | 144 | 153 |
| 70 | 149 | 184 | 196 |
| 95 | 179 | 223 | 238 |
| 120 | 206 | 259 | 276 |
| 150 | 225 | 299 | 319 |
| 185 | 255 | 341 | 364 |
| 240 | 297 | 403 | 430 |
| 300 | 339 | 464 | 497 |
Values follow IEC 60364-5-52 for PVC insulation, three loaded conductors and 30 °C ambient. B2: conduit in a wall, C: on a wall surface, E: perforated cable tray. Use the correction factor (k) for temperature, grouping or different insulation.
Common mistakes
- Looking only at current: on long runs voltage drop increases the size; check both criteria.
- Forgetting the correction factor: high ambient temperature or many cables laid together reduce capacity.
- Skipping the protective device: the chosen size must match the rating of the breaker or fuse.
- Not checking short-circuit withstand: small sizes may not survive a high fault current; assess the result with the short-circuit tool.
- Going below 16 mm² in aluminium: aluminium conductors below 16 mm² are not used; the tool does not list them.
Frequently asked questions
What does the correction factor (k) mean?
It is the multiplier applied to the current rating for ambient temperature, grouping of cables and similar conditions. Read it from the tables in the standard and enter the product; 1 means no correction.
What voltage drop is allowed?
It depends on regulations and the project specification; about 3 % for lighting and 5 % for other loads are common. The default is 3 %; adjust it to your project.
Can I use the result directly?
No. This tool is for preliminary sizing; short-circuit, protective-device coordination and the manufacturer's catalogue must be checked separately.
How do I choose a cable size?
Check both current-carrying capacity and permitted voltage drop; choose the smallest standard size that satisfies both.
What voltage drop is acceptable?
Usually 3% for lighting and up to 5% for other circuits; the final limit depends on the design and applicable regulation.
What are B2, C and E?
Installation methods: B2 conduit in a wall, C on a wall or ceiling surface, E perforated tray in free air. The method changes heat dissipation and so the capacity.
Can I use it for single-phase and DC?
Yes. The same capacity table is used, so the result stays on the safe side; the voltage-drop formula changes accordingly.
Guide: How to Size a Cable: Current Rating and Voltage Drop with a Worked Example