« Tools · Electrical Calculators
AWG to mm² Converter
Convert between American Wire Gauge (AWG) and metric cross-section (mm²); diameter, the nearest standard size and the full table on one page.
How to use
- Choose the direction: AWG → mm² or mm² → AWG.
- Select the AWG number or enter the mm² value.
- Cross-section, diameter, the nearest equivalent and a table appear.
Method and assumptions
- AWG diameter: d = 0.127 mm × 92^((36 − n) / 39); area = π·d²/4. For 1/0, 2/0, 3/0, 4/0 use n = 0, −1, −2, −3.
- Values are for solid conductors; stranded cables have a larger overall diameter.
- Current rating depends on insulation and installation; equal area does not mean equal ampacity. Resistance is for copper at 20 °C.
AWG – mm² reference
| AWG | Area (mm²) | Diameter (mm) |
|---|---|---|
| 10 | 5.261 | 2.588 |
| 12 | 3.309 | 2.053 |
| 14 | 2.081 | 1.628 |
| 16 | 1.309 | 1.291 |
| 18 | 0.823 | 1.024 |
| 20 | 0.518 | 0.812 |
| 22 | 0.326 | 0.644 |
| 24 | 0.205 | 0.511 |
The other way round: 2.5 mm² is about AWG 13 (2.62 mm²) and 1.5 mm² about AWG 15 (1.65 mm²). Standard metric sizes do not match AWG exactly.
How to read AWG
The higher the AWG number, the thinner the conductor: AWG 10 is thick, AWG 24 is thin. Every 6 numbers roughly halves the diameter. Heavy power cables use larger sizes such as 1/0, 2/0, 3/0 and 4/0.
Common mistakes
- Taking equal area as equal current: current capacity depends on insulation and installation.
- Treating stranded cable as solid: the table is for solid conductors; a stranded cable has a larger outer diameter.
- Thinking a bigger number is thicker: in AWG a bigger number is thinner.
- Settling for the nearest value: for safety-critical sizes pick the next standard size up.
Frequently asked questions
How many mm² is 12 AWG?
About 3.31 mm²; the next standard metric size up is 4 mm².
Which AWG is 2.5 mm²?
The nearest is 13 AWG (2.62 mm²); the common 14 AWG (2.08 mm²) is thinner.
Does a higher AWG number mean a thicker wire?
No, the opposite: the higher the number, the thinner the wire.
Does the cable get thicker as the AWG number rises?
No, it gets thinner. AWG 24 is much thinner than AWG 10.
More tools
© ZDK Mühendislik — the software of this tool may not be copied or reused on other sites without permission.