How to Do a Lighting Calculation: Lumen Method with Example

The most common preliminary method for finding how many luminaires a room needs is the lumen method. It starts from the target illuminance (lux) and finds the count from the luminaire's luminous flux (lumens).

Formula

N = E × A / (Φ × CU × MF)

  • E: target illuminance (lux)
  • A: room area (m²)
  • Φ: luminous flux of one luminaire (lumens)
  • CU: utilisation factor; how much light reaches the working plane (typically 0.4-0.7)
  • MF: maintenance factor; allowance for dirt and light loss over time (often around 0.8 for LED)

Example

A 10 × 8 m (80 m²) office, target 500 lux, a 4000 lm 36 W luminaire, CU = 0.6, MF = 0.8:

N = 500 × 80 / (4000 × 0.6 × 0.8) = 20.8 → 21 luminaires.

The resulting illuminance is about 504 lux, total power 756 W, power density about 9.5 W/m². The approximate layout is 4 rows × 6 columns; adjust the real layout to the room.

Typical target illuminance (guide)

Area Lux
Corridor 100
Stairs 150
WC / washroom 200
Storage (general) 100-200
Office, meeting room 500
Workshop 300-500
Indoor car park 75

These are typical values; regulations, specifications and the nature of the work may require other levels.

Common mistakes

  • Taking CU and MF as 1: the luminaire count comes out too low.
  • Mixing watts and lumens: the formula needs lumens; lm/W varies by luminaire.
  • Laying out without planning: distribute luminaires evenly and leave half a spacing at walls.

The lumen method gives average illuminance; use lighting software to check uniformity and glare.

Quick calculation

Enter room size, target lux and luminaire data in the Lighting Calculator (Lumen Method). For running cost use the Electricity Consumption Calculator.

Free tools related to this article

Support the Project!

If you find this free content useful and would like to contribute to the site's development and the addition of new content, you can support by buying a small coffee. Your support is very valuable to me!

Buy Me a Coffee

« Back to All Posts