Lighting Calculator (Lumen Method)

Enter the room size, target illuminance (lux) and the luminaire's luminous flux to find how many luminaires you need.

Calculations run in your browser; the data you enter is never sent to any server.

Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.

Get a Quote »
Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.

How to use

  1. Enter the room length and width.
  2. Enter the target illuminance (lux), the luminaire's luminous flux (lumens) and optionally its power (W).
  3. Adjust the utilisation and maintenance factors if needed; the luminaire count and approximate layout appear.

Method and assumptions

  • Formula: N = E × A / (Φ × CU × MF). E is the target lux, A the area (m²), Φ the luminaire flux (lm), CU the utilisation factor, MF the maintenance factor.
  • The utilisation factor is typically 0.4-0.7 depending on room shape, surface reflectances and luminaire; the maintenance factor for LED is often taken around 0.8.
  • The result is preliminary; verify uniformity, glare and standard requirements with lighting software.

Example

A 10 × 8 m (80 m²) office, target 500 lux, a 4000 lm 36 W luminaire, CU 0.6, MF 0.8. N = 500 × 80 / (4000 × 0.6 × 0.8) = 20.8 → 21 luminaires. The resulting illuminance is about 504 lux, total power 756 W, power density about 9.5 W/m². The approximate layout is 4 rows × 6 columns; adjust the real layout to the room.

Typical target illuminance (guide)

AreaLux
Corridor100
Stairs150
WC / washroom200
Storage (general)100-200
Office, meeting room500
Workshop300-500
Indoor car park75

Values are typical; regulations, specifications and the task may require other levels.

Common mistakes

  • Taking CU and MF as 1: the luminaire count comes out too low.
  • Entering watts instead of luminous flux: the formula needs lumens; lm/W varies by luminaire.
  • Laying out without planning: distribute luminaires evenly and leave half a spacing at walls.

Frequently asked questions

How many lux are needed where?

Typical values: corridor 100, stairs 150, WC 200, office and meeting room 500 lux; they vary with task and conditions. For binding values see the relevant standard and specification.

What is the utilisation factor (CU)?

It shows how much of the luminaire's light reaches the working plane. It is higher in light-coloured, small rooms with efficient luminaires.

Why a maintenance factor (MF)?

Luminaires get dirty and output falls over time; the calculation allows for this loss from the start.

Guide: How to Do a Lighting Calculation: Lumen Method with Example