« Tools · Electrical Calculators
Lighting Calculator (Lumen Method)
Enter the room size, target illuminance (lux) and the luminaire's luminous flux to find how many luminaires you need.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Enter the room length and width.
- Enter the target illuminance (lux), the luminaire's luminous flux (lumens) and optionally its power (W).
- Adjust the utilisation and maintenance factors if needed; the luminaire count and approximate layout appear.
Method and assumptions
- Formula: N = E × A / (Φ × CU × MF). E is the target lux, A the area (m²), Φ the luminaire flux (lm), CU the utilisation factor, MF the maintenance factor.
- The utilisation factor is typically 0.4-0.7 depending on room shape, surface reflectances and luminaire; the maintenance factor for LED is often taken around 0.8.
- The result is preliminary; verify uniformity, glare and standard requirements with lighting software.
Example
A 10 × 8 m (80 m²) office, target 500 lux, a 4000 lm 36 W luminaire, CU 0.6, MF 0.8. N = 500 × 80 / (4000 × 0.6 × 0.8) = 20.8 → 21 luminaires. The resulting illuminance is about 504 lux, total power 756 W, power density about 9.5 W/m². The approximate layout is 4 rows × 6 columns; adjust the real layout to the room.
Typical target illuminance (guide)
| Area | Lux |
|---|---|
| Corridor | 100 |
| Stairs | 150 |
| WC / washroom | 200 |
| Storage (general) | 100-200 |
| Office, meeting room | 500 |
| Workshop | 300-500 |
| Indoor car park | 75 |
Values are typical; regulations, specifications and the task may require other levels.
Common mistakes
- Taking CU and MF as 1: the luminaire count comes out too low.
- Entering watts instead of luminous flux: the formula needs lumens; lm/W varies by luminaire.
- Laying out without planning: distribute luminaires evenly and leave half a spacing at walls.
Frequently asked questions
How many lux are needed where?
Typical values: corridor 100, stairs 150, WC 200, office and meeting room 500 lux; they vary with task and conditions. For binding values see the relevant standard and specification.
What is the utilisation factor (CU)?
It shows how much of the luminaire's light reaches the working plane. It is higher in light-coloured, small rooms with efficient luminaires.
Why a maintenance factor (MF)?
Luminaires get dirty and output falls over time; the calculation allows for this loss from the start.
Guide: How to Do a Lighting Calculation: Lumen Method with Example