How Many Amps Is a kW? kW, kVA and Amps Conversion (Single and Three Phase)

"How many amps does an X kW load draw?" is the first step of cable and breaker selection. The answer depends on whether the system is single-phase, three-phase or DC, and on the power factor.

Formulas

  • Three-phase: P = √3 × U × I × cos φ → I = P / (√3 × U × cos φ)
  • Single-phase: P = U × I × cos φ → I = P / (U × cos φ)
  • DC: P = U × I

P is real power (W), U the voltage (line-to-line for three-phase, phase-neutral for single-phase) and cos φ the power factor. Apparent power S (kVA) and real power are related by P = S × cos φ.

Examples

  • 15 kW, 400 V, three-phase, cos φ = 0.85 → S = 17.6 kVA, I = 25.5 A
  • 100 A, 400 V, three-phase, cos φ = 0.8 → S = 69.3 kVA, P = 55.4 kW
  • 5 kVA, 230 V, single-phase, cos φ = 0.9 → P = 4.5 kW, I = 21.7 A
  • 2.4 kW, 24 V DC → I = 100 A

Rule of thumb

At 400 V three-phase with cos φ = 0.85, 1 kW ≈ 1.7 A. At 230 V single-phase with cos φ = 1, 1 kW ≈ 4.35 A.

Power (kW) Current (A), 400 V three-phase, cos φ 0.85
1.5 2.5
3 5.1
5.5 9.3
11 18.7
22 37.4
37 62.8

The table gives load current; for motors efficiency also counts, so the real current is higher.

Common mistakes

  • Taking cos φ as 1: current comes out too low.
  • Mixing line and phase voltage: enter 400 V for three-phase and 230 V for single-phase.
  • Treating kVA as kW: transformers and generators are rated in kVA, motors and heaters in kW.

Quick calculation

In the kW – kVA – Amps Converter enter the one value you know and see the others. For cable selection continue with the Cable Size Calculator.