How to Select Motor Current, Fuse and Contactor: Worked Example

When wiring a motor into a panel you decide three things: the current the motor draws, the fuse that suits it, and the contactor that switches it. The calculation is simple, but because of starting current the fuse is chosen noticeably larger than the rated current.

1. Rated current

For a three-phase motor:

In = P / (√3 × U × cos φ × η)

P is motor power (W), U the line-to-line voltage, cos φ the power factor and η the efficiency. The most reliable value is the current on the nameplate; use the formula only if it is missing.

Example: 11 kW, 400 V, cos φ = 0.85, η = 0.90 → In = 11,000 / (1.732 × 400 × 0.85 × 0.90) = 20.8 A.

2. Fuse

A motor draws several times its rated current while starting. So a gG fuse is chosen for about 2 × In on direct-on-line: 20.8 × 2 = 41.6 A → the next standard value, 50 A. Use about 1.6 for star-delta, 1.6 for a soft starter and 1.5 for a drive. These are guideline values; the equipment manufacturer's table prevails.

3. Contactor and thermal relay

The contactor's AC-3 current must exceed the motor current: 25 A for 20.8 A. The thermal relay is set to the motor's nameplate current; overload protection is done by the relay, not the fuse.

Quick table (400 V, direct on line, cos φ 0.85, η 0.90)

Power (kW) In (A) gG fuse (A) AC-3 contactor (A)
1.5 2.8 6 9
3 5.7 16 9
5.5 10.4 25 12
11 20.8 50 25
22 41.5 100 50
37 69.8 160 80

Star-delta example

30 kW, cos φ = 0.88, η = 0.92 → In = 53.5 A. The fuse is 100 A gG; the main and delta contactors need at least 0.58 × In = 31 → 32 A, the star contactor at least 0.33 × In = 17.6 → 18 A; the thermal relay is set to 0.58 × In ≈ 31 A.

Common mistakes

  • Choosing the fuse equal to rated current: the motor will blow it on starting.
  • Setting the thermal relay to the fuse value: the relay must be set to the motor current.
  • Choosing the cable from the fuse: the cable follows the motor current and voltage drop.

Quick calculation

Use the Motor Current, Fuse and Contactor Selection tool to see all values together from power, voltage and starting type. For cables see the Cable Size and Voltage Drop tool.

Free tools related to this article

Projeye Destek Olun!

Bu ücretsiz içeriği faydalı buluyorsanız ve sitenin gelişimine, yeni içerikler eklenmesine katkıda bulunmak isterseniz, küçük bir kahve ısmarlayarak destek olabilirsiniz. Desteğiniz benim için çok değerli!

Bir Kahve Ismarla

« Tüm Yazılara Geri Dön