Choosing a cable size means meeting two conditions at once: the cable must carry the load current without overheating, and the voltage drop at the end of the run must stay within the allowed limit. On short runs the current rating usually governs; on long runs voltage drop does. Here are both checks step by step.
1. Find the load current
For a three-phase load:
I = P / (√3 × U × cos φ)
Example: 15 kW, 400 V, cos φ = 0.85 → I = 15,000 / (1.732 × 400 × 0.85) = 25.5 A
2. Select by current-carrying capacity
Capacity depends on conductor material, insulation and installation method. Per IEC 60364-5-52, for PVC insulated copper cable clipped to a wall (method C) with three loaded conductors:
- 2.5 mm² → 24 A
- 4 mm² → 32 A
- 6 mm² → 41 A
For 25.5 A, 2.5 mm² is not enough; 4 mm² is the first suitable size. If the ambient is above 30 °C or cables are grouped, the rating is reduced by a correction factor.
3. Check the voltage drop
ΔU = √3 × I × L × (R × cos φ + X × sin φ), where R = ρ / S.
On a 50 m run the drop for 4 mm² copper is about 2.66%, below the 3% limit, so 4 mm² is acceptable.
What if the run is longer?
With the same load 120 m away, the drop would be 6.4% on 4 mm² and 4.3% on 6 mm². Only 10 mm² (2.6%) meets the 3% limit. A size that is fine for current has to grow two steps on a long run because of voltage drop.
Common mistakes
- Checking current only and ignoring voltage drop
- Neglecting correction factors (temperature, grouping)
- Forgetting the go-and-return length on single-phase circuits
- Not checking short-circuit withstand and coordination with the protective device
Quick calculation
The Cable Size & Voltage Drop Calculator shows the current, the suitable size and the voltage drop of every size for three-phase, single-phase and DC. For motors, find the rated current first with the motor current tool.
Results are for preliminary sizing; the final design must follow the applicable standards and manufacturer data.