"How long will the UPS run when power fails?" depends on battery energy, load power and losses. The calculation gives a first idea; the real time must be verified with the manufacturer's discharge table.
Formula
Runtime (h) = V × Ah × n × usable fraction × efficiency / load (W)
- V: battery bank voltage
- Ah: capacity of one string, n the number of parallel strings
- Usable fraction: the part that may be drawn from the battery (usually 50-80% for lead-acid)
- Efficiency: inverter efficiency (typically around 90%)
- Load: in watts; if VA is given, W = VA × power factor (usually 0.8-0.9 for UPS)
Example
A 48 V 100 Ah bank (4800 Wh), 80% usable discharge, 90% inverter efficiency, 1000 W load:
- Usable energy = 4800 × 0.8 × 0.9 = 3456 Wh
- Runtime = 3456 / 1000 = 3.46 h ≈ 207 minutes
Reversed: for 60 minutes the energy needed is 1000 / (0.8 × 0.9) = 1389 Wh, about 29 Ah at 48 V.
Battery connection
- Series: voltage adds, capacity stays the same (4 × 12 V 100 Ah = 48 V 100 Ah).
- Parallel: capacity adds, voltage stays the same.
Use batteries of the same make, model and age together.
Why is the real runtime shorter?
- At high discharge current battery capacity falls below nominal.
- Low temperature and battery ageing reduce capacity.
- Fully discharging the battery shortens its life.