UPS / Battery Runtime Calculator
Enter the battery bank voltage and capacity and the load power; see the runtime and the Ah needed for a target time.
Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.
Get a Quote »How to use
- Enter the bank's total voltage (V), the capacity of one string (Ah) and the number of parallel strings.
- Enter the load power (W), the inverter efficiency and the usable depth of discharge.
- If you enter a target time (min), the Ah needed for it is also calculated.
Method and assumptions
- Runtime = battery energy (V × Ah) × usable fraction × efficiency / load power.
- Load power is in watts; if VA is given, W = VA × power factor (typically 0.8-0.9 for UPS).
- Real runtime is usually shorter: high discharge current, low temperature and battery ageing reduce capacity; the result is preliminary.
Example
A 48 V 100 Ah bank (4800 Wh), 90% inverter efficiency, 80% usable discharge and a 1000 W load: usable energy is 4800 × 0.8 × 0.9 = 3456 Wh; runtime is 3456 / 1000 = 3.46 h ≈ 207 minutes. For 60 minutes the energy needed is 1000 / (0.8 × 0.9) = 1389 Wh, about 29 Ah at 48 V.
Battery connection
| Connection | Voltage | Capacity |
|---|---|---|
| Series | Adds | Stays the same |
| Parallel | Stays the same | Adds |
Use batteries of the same make, model and age together; mixed ages limit the bank to the weakest battery.
Common mistakes
- Using battery Ah as if it were watts: multiply by voltage first (Wh = V × Ah).
- Entering VA instead of W: the runtime comes out too short; convert with the power factor.
- Calculating for full discharge: it shortens life; keep the usable fraction low.
Frequently asked questions
How far can a lead-acid battery be discharged?
To preserve life, about 50-80% of capacity is usually used; lithium batteries may allow more. Check the manufacturer's data.
What happens when 12 V batteries are connected in series?
Voltage adds and capacity (Ah) stays the same: four 12 V 100 Ah in series give 48 V 100 Ah. In parallel the Ah adds.
Why does the real runtime differ from the calculation?
At high current battery capacity falls below nominal, and efficiency and ageing matter; a light load lasts longer. The manufacturer's discharge table prevails.
Guide: How Long Does a UPS Battery Last? Runtime Calculation