UPS / Battery Runtime Calculator

Enter the battery bank voltage and capacity and the load power; see the runtime and the Ah needed for a target time.

Calculations run in your browser; the data you enter is never sent to any server.

Get a quote for solar PV design, power factor correction and electrical contracting for your facility; engineering consultancy is also available.

Get a Quote »
Results are for preliminary design and checking only. Final design must follow the applicable standards, the manufacturer's catalogue and approval by a qualified engineer; ZDK Mühendislik accepts no liability for how results are used.

How to use

  1. Enter the bank's total voltage (V), the capacity of one string (Ah) and the number of parallel strings.
  2. Enter the load power (W), the inverter efficiency and the usable depth of discharge.
  3. If you enter a target time (min), the Ah needed for it is also calculated.

Method and assumptions

  • Runtime = battery energy (V × Ah) × usable fraction × efficiency / load power.
  • Load power is in watts; if VA is given, W = VA × power factor (typically 0.8-0.9 for UPS).
  • Real runtime is usually shorter: high discharge current, low temperature and battery ageing reduce capacity; the result is preliminary.

Example

A 48 V 100 Ah bank (4800 Wh), 90% inverter efficiency, 80% usable discharge and a 1000 W load: usable energy is 4800 × 0.8 × 0.9 = 3456 Wh; runtime is 3456 / 1000 = 3.46 h ≈ 207 minutes. For 60 minutes the energy needed is 1000 / (0.8 × 0.9) = 1389 Wh, about 29 Ah at 48 V.

Battery connection

ConnectionVoltageCapacity
SeriesAddsStays the same
ParallelStays the sameAdds

Use batteries of the same make, model and age together; mixed ages limit the bank to the weakest battery.

Common mistakes

  • Using battery Ah as if it were watts: multiply by voltage first (Wh = V × Ah).
  • Entering VA instead of W: the runtime comes out too short; convert with the power factor.
  • Calculating for full discharge: it shortens life; keep the usable fraction low.

Frequently asked questions

How far can a lead-acid battery be discharged?

To preserve life, about 50-80% of capacity is usually used; lithium batteries may allow more. Check the manufacturer's data.

What happens when 12 V batteries are connected in series?

Voltage adds and capacity (Ah) stays the same: four 12 V 100 Ah in series give 48 V 100 Ah. In parallel the Ah adds.

Why does the real runtime differ from the calculation?

At high current battery capacity falls below nominal, and efficiency and ageing matter; a light load lasts longer. The manufacturer's discharge table prevails.